ABB i-bus
®
KNX
Start-up
24 2CDC508116D0203 | FCL/S x.6.1.1
Limitation on forced operation
Options:
3, 2, 1, OFF
Unchanged
OFF
1
1, OFF
2
2, 1
2, 1, OFF
3
3, 2
3, 2, 1
This parameter sets which fan speed is set, or may not be over/undershot, when forced operation is
active.
3, 2, 1, OFF:
All states are feasible.
Unchanged
: The state is retained.
OFF
: Off
1
: Limited to speed 1.*
1, OFF
: Limited to speed 1 and off.
2
: Limited to speed 2.*
2, 1
: limited to speeds 2 and 1.
2, 1, OFF
: limited to speeds 2, 1 and off.
3
: Limited to speed 3.*
3, 2
: limited to speeds 3 and 2.
3, 2, 1
: limited to speeds 3, 2 and 1.
* The control value is ignored.
Enable automatic operation
Options:
No
Yes
Yes
:
Automatic operation
Parameter window - Automatic control (Multi-level)
p.30 appears.
Enable direct operation
Options:
No
Yes
Yes
:
Direct operation
Parameter window - Direct operation
on p.38 appears.
Set startup/run-on
Options:
No
Yes
Yes
: The
Set startup/run-on
Parameter window - Startup/Run-on
on p.40
appears.