ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 79
No.
Function
Object name
Data type
Flags
40
Switch
Output B
1 bit
DPT 1.001
C, W
The communication object is enabled if the parameter
Output B
has been enabled in the parameter window
Enable Outputs
A...F.
This communication object is used for switching the output ON/OFF. The device receives a switch telegram via a switch
communication object.
N/O:
Telegram value
1 = switch ON
0 = switch OFF
N/C:
Telegram value
1 = switch OFF
0 = switch ON
Note
With logical connections or forced operations, modifying communication object
Switch
does not necessarily result in
a changed contact position.
For further information see:
41
Permanent ON
Output B
1 bit
DPT 1.003
C, W
The communication object is enabled if the parameter
Enable function Time
in the
B: Output
parameter window is set to
Yes
.
The output can be forcibly switched on with this communication object.
If the communication object is assigned with the value 1, the output is switched on irrespective of the value of the communi-
cation object
Switch
and remains switched on until the communication object
Permanent ON
has the value 0. When the
Permanent ON state ends, the state of the communication object
Switch
is used.
Permanent ON
only switches ON and "masks" the other functions. This means that the other functions, e.g. Staircase light-
ing, continue to run in the background but do not initiate a switching action. When Permanent ON ends, the contact position
which would result without the Permanent ON function becomes active. For the
Staircase lighting
function, the response after
Permanent ON can be parameterized in
Parameter window B: Output - Time
This communication object can be used, for example, to allow service or maintenance and cleaning personnel to initiate a
permanent ON. The device receives a switch telegram via the Switch object.
Permanent ON becomes inactive after a download or bus voltage recovery.
Telegram value
1 = activates permanent ON mode
0 = deactivates permanent ON mode