ABB i-bus
®
KNX
Start-up
68 2CDC508116D0203 | FCL/S x.6.1.1
No.
Function
Communication object name
Data type
Flags
14
54
Fan speed up/down
Fan A
Fan CDE
1 bit
DPT 1.007
C, W
The communication object is enabled if the parameters
Enable direct operation
and
Enable communication object "Fan
speed up/down" 1 bit
in the
A: Fan
or
CDE: Fan
parameter window are set to
Yes
.
With this communication object, the fan can be switched one fan speed further up or down via a 1 bit telegram. Switching
(up/down) is determined by the telegram value.
With multiple manual up or down switching, the required speed will be increased or reduced by a speed step. This is feasible
until the maximum or minimum possible speed is reached. The parameterized limitations are taken into account here. Fur-
ther up or down telegrams are ignored and not executed. Each new switching telegram initiates a recalculation of the re-
quired speed.
Telegram value:
0 = switch fan speed down
1 = switch fan speed up
15
55
Status fan ON/OFF
Fan A
Fan CDE
1 bit
DPT 1.001
C, T
The communication object is enabled if the parameter
Enable communication object "Status fan On/Off" 1 bit
in the
– Status
message
s parameter window is set to
Yes
.
The communication object receives the communication object value 1 (ON), if at least one fan speed is not equal to zero
(OFF). The value of the communication object is sent if not equal to zero. This communication object thus indicates the sta-
tus of the fan, whether it is switched on or off.
Telegram value:
0 = OFF
1 = ON
Note
Some fans require an ON telegram before you set a fan speed. Using the communication object
Status fan ON/OFF
,
the fan can, for example, be switched on centrally with a switch actuator via the main switch.
16
56
Status Fan speed
Fan A
Fan CDE
1 byte
DPT 5.010
C, R, T
The communication object is enabled if the parameter
Enable communication object "Status fan speed" 1 byte
in parameter
window
Status messages
is set to
Yes.
You can parameterize whether the communication object value is updated only, or sent on the bus, After a change or re-
quest. It is possible to parameterize whether the actual or required speed is displayed with the status communication object.
This communication object allows you, for example, to display the fan speed as a figure value.
The following telegram values apply for the 1 byte communication object:
Figure value
Hexadecimal
Binary value bit
76543210
Fan speed
0
00
00000000
0 (OFF)
1
01
00000001
Fan speed 1
2
02
00000010
Fan speed 2
3
03
00000011
Fan speed 3