ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 77
No.
Function
Object name
Data type
Flags
29
69
Control value A
(if 2 control values) or
Control value
(if only 1 control value)
Fan A
Fan CDE
1 byte
DPT 5.010
C, W
The communication object is enabled if the parameter
Enable automatic operation
has been enabled in the
Fan
parameter
window.
Using this communication object the control value for automatic operation is predefined as a 1 byte value [0...255].
30
70
Control value B
(if 2 control values)
Fan A
Fan CDE
1 byte
DPT 5.010
C, W
The communication object is enabled if the parameter
Enable automatic operation
has been enabled in the
Fan
parameter
window and two outputs have been activated via the
Number of control value inputs
parameter in the
Automatic control
pa-
rameter window.
Using this communication object the second control value for automatic operation is predefined as a 1 byte value [0...255].
31
71
Toggle control value A/B
(if 2 control values)
Fan A
Fan CDE
1 bit
DPT 1.001
C, W
The communication object is enabled if two control value (A and B) communication objects have been activated in the
Auto-
matic control
parameter window, and they are to be selected by a communication object.
Telegram value:
0 = Control value A
1 = Control value B
32
72
Fault control value
Fan A
Fan CDE
1 bit
DPT 1.005
C, R, T
The communication object is enabled if the parameter
Activate monitoring control values
in parameter window
Automatic
control
is set to
Yes.
This communication object displays control value faults
The blower actuator uses the
Fault control value
communication object to report a fault and then responds according to the
parameterization for faults.
Telegram value:
0 = no fault
1 = fault
Note
If no value is sent to the communication object
Control value A,
Control value B
or
Control Value
for a set time, a
sender fault is assumed. If communication object 31,
Toggle control value A/B
, receives a value, the monitoring time
is started.