10 2CDC508116D0203 | FCL/S x.6.1.1
2.1.2
Lamp output load
at 230 V AC
Lamps
Incandescent lamp load
1200 W
Fluorescent lamps T5/T8
Uncorrected
Parallel compensated
DUO circuit
800 W
300 W
350 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
Halogen lamps 230 V
800 W
1000 W
1000 W
Dulux lamp
Uncorrected
Parallel compensated
800 W
800 W
Mercury-vapor lamp
Uncorrected
Parallel compensated
1000 W
800 W
Switching capacity (switching contact)
Maximum peak inrush current I
p
(150
s)
Maximum peak inrush current I
p
(250
s)
Maximum peak inrush current I
p
(600
s)
200 A
160 A
100 A
Number of electronic ballasts
(T5/T8, single element)
1)
18 W (ABB EVG 1 x 18 SF)
24 W (ABB EVG-T5 1 x 24 CY)
36 W (ABB EVG 1 x 36 CF)
58 W (ABB EVG 1 x 58 CF)
80 W (Helvar EL 1 x 80 SC)
10
10
7
5
3
1)
For multiple element lamps or other types the number of electronic ballasts must be determined using the peak inrush current of the ballasts.
Device type
Application
Maximum number of
Communication objects
Maximum number of
group addresses
Maximum number of
associations
FCL/S 1.6.1.1
Switch Blower 1f 6A/1.0*
64
254
254
FCL/S 2.6.1.1
Switch Blower 2f 6A/1.0*
124
254
254
* … = current version number of the application.
Please refer the software information on our homepage for this purpose.
Note
ETS and the current version of the device application are required for programming.
The current version of the application is available for download at
www.abb.com/knx
. After import into
ETS it appears in the
Catalogs
window under
Manufacturers/ABB/Heating
,
Ventilation, Air condition-
ing/Ventilation actuator.
The device does not support the locking function of a KNX device in ETS. If you use a
BCU code
to
inhibit access to all the project devices, it has no effect on this device. Data can still be read and pro-
grammed.