Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 67
3.3.3
Communication objects Fan A and Fan CDE
Note
Only the FCL/S 2.6.1.1 2-fold actuator can control the second Fan CDE.
All three fan speeds can also be individually parameterized as outputs C, D and E. See
, p.78 for descriptions of the communication objects.
The settings options are described in
Parameter window Enable outputs A...F
3.3.3.1
Communication objects
Fan Multi-level
No.
Function
Communication object name
Data type
Flags
10
50
Fan speed switch
Fan A
Fan CDE
1 byte
DPT 5.010
C, W
The communication object is enabled if the parameters
Enable direct operation
and
Enable communication object "Switch
speed" 1 byte
in the
A: Fan
or
CDE: Fan
parameter window are set to
Yes
.
With this communication object, the fan can be switched on via a 1 byte communication object of a fan speed. If another fan
speed is switched on, at this point it will be switched off. The new fan speed is switched on taking the start-up phase into
account.
Limitati
ons through forced operation or one of the four limitations 1…4 are retained. Automatic operation is disabled. Com-
munication object
Automatic ON/OFF
reactivates automatic operation.
The following telegram values result:
1 byte value
Hexadecimal
Binary value bit
76543210
Fan speed
0
00
00000000
0 (OFF)
1
01
00000001
Fan speed 1
2
02
00000010
Fan speed 2
3
03
00000011
Fan speed 3
>3
>03
>00000011
Values greater than 3 are ignored
11
51
Switch speed 1
Fan A
Fan CDE
1 bit
DPT 1.001
C, W
The communication object is enabled if the parameters
Enable direct operation
and
Enable communication object "Switch
speed x" 1 bit
in the
Fan: A
or
Fan: CDE
parameter window are set to
Yes
.
Via the 1 bit communication object the device can receive a control value for fan speed 1.
Limitations through forced operation or one of the four limitations 1…4 are retained. Automatic operation is disabled. Com-
munication object
Automatic ON/OFF
reactivates automatic operation.
If several ON telegrams are received consecutively in a short period of time at various
Switch speed x
(x = 1...3) communica-
tion objects, the value last received is the one that will control the fan. An OFF telegram to one of the three communication
objects
Switch speed x
(x = 1...3) switches the fan off.
Telegram value:
0 = fan OFF
1 = fan ON in speed 1
12
52
Switch speed 2
See communication object 11
13
53
Switch speed 3
See communication object 11