FCL/S x.6.1.1 | 2CDC508116D0203 9
Output switching times
3)
Maximum output relay position change per mi-
nute if all relays are switched simultaneously.
The position changes should be distributed
equally within the minute.
1.6.1.1
2.6.1.1
60
30
Maximum output relay position change per mi-
nute if only one relay is switched.
240
240
Connections
KNX
Via bus connection terminals,
0.8 mm Ø, solid
Load circuits
Screw terminal
0.2…2.5 mm
2
fine stranded
0.2...4 mm
2
solid
Tightening torque
max. 0.6 Nm
Operating and display elements
Programming
Button/LED
For assignment of the physical address
Degree of protection
IP 20
To EN 60 529
Protection class
II
To EN 61 140
Isolation category
Overvoltage category
III to EN 60 664-1
Pollution degree
2 to EN 60 664-1
KNX safety extra low voltage
SELV 24 V DC
Temperature range
Operation
Storage
Transport
-5
°C…+45 °C
-25 °C
…+55 °C
-25 °C
…+70 °C
Ambient conditions
Maximum air humidity
95 %, no condensation allowed
Design
Modular installation device (MDRC)
Modular installation device, Pro
M
FCL/S Type
1.6.1.1
2.6.1.1
Dimensions
90 x W x 64.5 mm (H x W x D)
Width W in mm
72
108
Mounting width in units (18 mm modules)
4
6
Mounting depth in mm
64.5
64.5
Weight
1.6.1.1
2.6.1.1
in kg
0.13
0.24
Installation
On 35 mm mounting rail
To EN 60 715
Mounting position
As required
Housing/color
Plastic housing, gray
Approvals
KNX to EN 50 090-1, -2
Certification
CE mark
In accordance with the EMC guideline and low
voltage guideline
3)
The specifications apply only after the bus voltage has been applied to the device for at least 30 seconds. Typical relay delay is approx. 20 ms.