ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 69
No.
Function
Communication object name
Data type
Flags
17
57
Status Fan speed 1
Fan A
Fan CDE
1 bit
DPT 1.001
C, R, T
The communication object is enabled if the parameter
Enable communication object "Status fan speed x" 1 bit
in the
Status
messages
parameter window is set to
Yes
.
You can parameterize whether the communication object value is updated but not sent, sent on request, or only sent when
changed.
You can also parameterize whether the status should indicate a current fan speed or a required fan speed. This communica-
tion object allows you to display the fan speed in a visualization or to indicate it on a display.
Telegram value:
0 = fan speed OFF
1 = fan speed ON
18
58
Status Fan speed 2
See communication object 17
19
59
Status Fan speed 3
See communication object 17
20
60
Run-on
Fan A
Fan CDE
1 bit
DPT 1.003
C, W
The communication object is enabled if run-on behavior has been enabled in parameter window
A: Fan - Startup/Run-on
or
CDE: Fan - Startup/Run-on
.
If run-on behavior is enabled, it will be activated after an ETS reset or by an ON telegram on this communication object.
Telegram value:
0 = run-on disabled
1 = run-on enabled
21
61
Limitation 1
Fan A
Fan CDE
1 bit
DPT 1.003
C, W
The communication object is enabled if the parameter
Enable limitations
in parameter window
Automatic control
is set to
Yes.
Note
Limitation 1 is only active in automatic operation.
Limitation 1 is active when communication object
Limitation 1
receives
a telegram with the value 1, and is lifted when the
same communication object receives a telegram with the value 0.
When Limitation 1 is activated, the fan can only assume the fan speed or speed range as set in the parameter
Speed with
limitation 1
.
Telegram value:
0 = limitation x inactive
1 = limitation x active
22
62
Limitation 2
See communication object 21
23
63
Limitation 3
See communication object 21
24
64
Limitation 4
See communication object 21