FCL/S x.6.1.1 | 2CDC508116D0203 37
Fan speed with limitation 1
Fan speed with limitation 2
Fan speed with limitation 3
Fan speed with limitation 4
Options:
3, 2, 1, OFF
Unchanged
OFF
1
1, OFF
2
2, 1
2, 1, OFF
3
3, 2
3, 2, 1
This parameter sets the fan speed or speed range that applies under active limitation.
3, 2, 1, OFF:
All states are possible.
Unchanged
: The state is retained.
OFF
: Off
1
: Limited to speed 1.*
1, OFF
: Limited to speed 1 and off.
2
: Limited to speed 2.*
2, 1
: limited to speeds 2 and 1.
2, 1, OFF
: limited to speeds 2, 1 and off.
3
: Limited to speed 3.*
3, 2
: limited to speeds 3 and 2.
3, 2, 1
: limited to speeds 3, 2 and 1.
* The control value is ignored.