ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 23
Fan speed on bus voltage recovery
Options:
Unchanged
OFF
1
2
3
Unchanged
: The fan's speeds remain unchanged.
OFF
: The fan is switched off.
1, 2 or 3
: The fan switches to fan speed 1, 2 or 3.
Caution
The device is supplied ex-works with a default setting (factory default). This ensures that the fan setting
is switched off when the bus voltage is applied to the relay for the first time, preventing any unintentional
switch-on damage to the device during transport, e.g. due to vibration.
It is advisable to apply a bus voltage before connecting the fan, in order to assign it a defined switch
state. This eliminates the possibility of an incorrect contact setting destroying the fan.
Enable communication object
"Forced operation" 1 bit
Options:
No
Yes
Yes
: The 1 bit
Forced operation
communication object is enabled. The following parameters appear:
Forced operation on object value
Options:
1
0
1
: Forced operation is activated by a telegram with value 1.
0
: Forced operation is activated by a telegram with value 0.
Note
During forced operation the settings set in
Automatic control
are ignored. Automatic control is
updated after forced operation has been rescinded.
Important
Forced operation remains active until:
the opposite value is sent;
the assignment is changed;
the fan type is changed.
Forced operation is not deactivated by a download of the application, in which the fan type and
the respective group addresses are retained.
Forced operation is reset if an ETS reset has occurred.