38 2CDC508116D0203 | FCL/S x.6.1.1
3.2.2.1.3
Parameter window
- Direct operation
This parameter window is visible if the
Enable direct operation
, p.21 is set to
Yes
.
Enable communication objects
"Switch speed x" 1 bit
Options:
No
Yes
Yes
: Three 1 bit communication objects,
Switch speed x
(x = 1...3) are enabled.
The device receives a setting telegram via these communication objects.
Telegram value
1 = Fan speed x is switched on
0 = fan speed x is switched off
If several ON/OFF telegrams are received consecutively in a short period of time at various
Fan speed
1...3
communication objects, the value last received will be the one used to control the fan. An OFF tele-
gram to one of the three communication objects
Fan speed 1...3
switches the fan off.
Important
Forced operation remains valid and is taken into account.
The parameterized minimum fan speed dwell time for automatic operation is ignored during manual
operation. Accordingly, an immediate reaction to manual operation is detected.
The delay time with speed switchover remains active to protect the fan.