ACH580 Installation, Operation and Maintenance Manual
19
ACH580-01 Installation
Power cable terminal and lead-through data
Input, motor, resistor and DC cable lead-throughs, maximum wire sizes (per phase)
and terminal screw sizes.
Note:
Minimum wire size does not necessarily have enough current capability for full
load. Make sure the installation complies with local laws and regulations.
Frame
size
Cable lead-
throughs
L1, L2, L3, T1/U, T2/V, T3/W terminals
1)
Grounding
terminals
1)
Per
cable
type
Max cable
dia.
Min wire size
(solid/stranded)
Max wire size
(solid/stranded)
Max wire size
pcs
in.
mm
AWG
mm
2
AWG
mm
2
AWG
mm
2
R1
1
1.18
30
14
2.1
10
6/4
6/6
16/16
R2
1
1.18
30
14
2.1
6
16/16
6/6
16/16
R3
1
1.18
30
14
2.1
2
35/25
2/2
35/35
R4
1
1.77
45
14
2.1
1
50
2/2
35/35
R5
1
1.77
45
14
2.1
2/10
70
2)
2)
R6
1
1.77
45
4
25
300 MCM
150
2)
2)
R7
1
2.13
54
3/0
95
500 MCM
240
2)
2)
R8
2
1.77
45
2×1/0
2×50
2×300 MCM
2×150
2)
2)
R9
2
2.13
54
2×3/0
2×95
2×500 MCM
2×240
2)
2)
1) Screwdrivers: R1 - Slot 4 mm and PH1; R2 - 4.5 mm and PH2; R3, R4 - PH2
2) Either cable lug (R5) or clamp (R6…R9) is used for grounding.
Frame
size
Cable lead-
throughs
R+, R-, UDC+ and UDC- terminals
1)
Per
cable
type
Max cable
dia.
Min wire size
(solid/
stranded)
Max wire size
(solid/stranded)
Hardware
Torque
pcs
in.
mm
AWG
mm
2
AWG
mm
2
M…
lb-ft
N·m
R1
1
0.906
23
14
2.1
10
6/4
1)
0.4
1.2…1.5
R2
1
0.906
23
14
2.1
6
16/16
1)
1.1
1.2…1.5
R3
1
0.906
23
14
2.1
2
35/25
1)
3.3
2.5…4.5
R4
1
1.54
39
14
2.1
1
50
1)
3.0
4.0
R5
1
1.54
39
14
2.1
2/10
70
M5
4.1
5.6
R6
1
1.77
45
4
25
300 MCM
150
M8
22.1
30
R7
1
2.13
54
3/0
95
500 MCM
240
M10
29.5
30
R8
2
1.77
45
2×1/0
2×50 2×300 MCM 2×150
M10
29.5
40
R9
2
2.13
54
2×3/0
2×95 2×500 MCM 2×240
M12
51.6
70
1) Screwdrivers: R1 - Slot 4 mm and PH1; R2 - 4.5 mm and PH2; R3, R4 - PH2