ACH580 Installation, Operation and Maintenance Manual
107
ACH580 E-Clipse Bypass
575 Volt fuses for box enclosures
ACH580-BxR-065A-4
65
50
R4
Class T
90A
Class J
100A
ACH580-BxR-077A-4
77
60
R4
Class T
100A
Class J
100A
ACH580-BxR-096A-4
96
75
R5
Class T
150A
Class J
225A
ACH580-BxR-124A-4
124
100
R6
Class T
200A
Class J
300A
ACH580-BxR-156A-4
156
125
R7
Class T
225A
Class J
350A
ACH580-BxR-180A-4
180
150
R7
Class T
300A
Class J
350A
ACH580-BxR-240A-4
240
200
R8
Class T
350A
Class J
400A
1) “BxR” represents both BCR and BDR.
Type Code
1
Nominal Output
Ratings
Base
Drive
Frame
Size
Internal Drive
Fuse Rating
External Fuse for
Disconnect Option
Drive
Current
Package
Power
Class
Max
Current
Rating
Class
Max
Current
Rating
A
HP
575 Volts
2
ACH580-BxR-02A7-6
2.7
2
R2
Class CC
15A
Class J
15A
ACH580-BxR-03A9-6
3.9
3
R2
Class CC
15A
Class J
15A
ACH580-BxR-06A1-6
6.1
5
R2
Class CC
15A
Class J
15A
ACH580-BxR-09A0-6
9
7.5
R2
Class CC
15A
Class J
20A
ACH580-BxR-011A-6
11
10
R2
Class CC
15A
Class J
25A
ACH580-BxR-017A-6
17
15
R2
Class CC
30A
Class J
40A
ACH580-BxR-022A-6
22
20
R3
Class T
40A
Class J
50A
ACH580-BxR-027A-6
27
25
R3
Class T
40A
Class J
60A
ACH580-BxR-032A-6
32
30
R3
Class T
40A
Class J
60A
ACH580-BxR-041A-6
41
40
R5
Class T
50A
Class J
100A
ACH580-BxR-052A-6
3
52
50
R5
Class T
80A
Class J
100A
ACH580-BxR-062A-6
62
60
R5
Class T
80A
Class J
150A
ACH580-BxR-077A-6
77
75
R5
Class T
100A
Class J
175A
ACH580-BxR-099A-6
99
100
R7
Class T
150A
Class J
225A
ACH580-BxR-125A-6
125
125
R7
Class T
175A
Class J
300A
ACH580-BxR-144A-6
144
150
R8
Class T
200A
Class J
350A
1) “BxR” represents both BCR and BDR.
2) BCR is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye source only.
3) BCR supports Delta network configuration.
Type Code
1
Nominal Output
Ratings
Base
Drive
Frame
Size
Internal Drive
Fuse Rating
External Fuse for
Disconnect Option
Drive
Current
Package
Power
Class
Max
Current
Rating
Class
Max
Current
Rating
A
HP