ACH580 Installation, Operation and Maintenance Manual
141
ACH580-PCR/PDR
PB1/PB2
ACH580 Drive
Disconnect
Output
Ground Lug
Input
Terminals
Input
Ground Lug
Motor
Terminals
Switch or
Circuit
T1 T2 T3
The alternate (HI) setting further reduces the
likelihood of condensate in high humidity
environments.
RHTR Temperature
HI/LO Jumber (X1)
Heater ON
Temperature
Heater OFF
Temperature
Default Setting
(X1 jumper in LO
position)
14.4 °C
58 °F
21.4 °C
70.5 °F
Alternate Setting
(X1 jumper in HI
position)
17.8 °C
64 °F
24.4 °C
76.5 °F
(PxB3R-1, PxB3R-2)
Motor
Terminals
Motor
Ground Lug
MOV and Line Reactor
(Optional)
Breaker
Service
Switch
(Optional)
Fuses