150
ACH580 Installation, Operation and Maintenance Manual
ACH580-PCR/PDR
Maintenance
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB for ACH580
enclosures in addition to the intervals on page
Enclosure air filter replacement B3 – UL (NEMA) Type 12 hinged door
wall mount enclosures
Filter material
This procedure applies to drive with input disconnect configurations in UL (NEMA)
Type 12 hinged door wall mount enclosures. This filter is located at the bottom of the
enclosure. Use the following procedure to check and replace filters.
1. On the enclosure, remove the screws holding the filter bracket in place.
2. Remove the filter kit from the enclosure.
3. Lift the filter out of the filter bracket and replace as appropriate.
4. With the filter in the filter bracket, reinstall filter kit onto enclosure.
5. Replace the mounting screws. Tighten to the recommended torque of 2 N•m
(1.47 ft-lbs) per installation instruction 3AXD50000221370.
Diagnostics
Maintenance
Configuration
Interval
Instruction
Check/replace hinged
door wall mount
enclosure inlet air filter
Hinged door wall
mount UL (NEMA)
Type 12 enclosures
Check every 3
months. Replace
as needed.
Enclosure air filter replacement
page
.
Material
Filter Type
American Air Filter (358-35-06A-12A)
POLYKLEON WHITE 12.7mm (1/2 in.) X 152.4mm (6 in.) X
304.6mm (12 in.) stk.
Mounting
Screws (4X)
Filter Bracket
Back of
Enclosure
Enclosure Door
Bottom of Enclosure