102
ACH580 Installation, Operation and Maintenance Manual
ACH580 E-Clipse Bypass
Type Code
1
Nominal Output
Ratings
Base
Drive
Frame
Size
Maximum Wire Size and Terminal Torque
Drive
Current
Package
Power
Circuit
Breaker
UL
(NEMA)
Type
1 and 12
Circuit
Breaker
UL
(NEMA)
Type 3R
Disconnect
Switch
UL (NEMA)
Type
1 and 12
Disconnect
Switch
UL (NEMA)
Type 3R
Motor
Terminals
UL (NEMA)
Type
1 and 2
Motor
Terminals
UL (NEMA)
Type 3R
Ground
Lugs
UL
(NEMA)
Type
1 and 2
Ground
Lugs
UL
(NEMA)
Type 3R
A
HP
460 Volts
ACH580-BxR-02A1-4
2.1
1
R1
#12
62 in-lbs
#12
62 in-lbs
#10
55 in-lbs
#10
55 in-lbs
#6
11-13 in-lbs
#6
11-13 in-lbs
#4
35 in-lbs
#4
35 in-lbs
ACH580-BxR-03A0-4
3.0
1.5
R1
ACH580-BxR-03A5-4
3.5
2
R1
ACH580-BxR-04A8-4
4.8
3
R1
ACH580-BxR-07A6-4
7.6
5
R1
ACH580-BxR-012A-4
12
7.5
R1
ACH580-BxR-014A-4
14
10
R2
#10
62 in-lbs
#10
62 in-lbs
#8
55 in-lbs
#8
55 in-lbs
ACH580-BxR-023A-4
23
15
R2
#6
55 in-lbs
#6
55 in-lbs
ACH580-BxR-027A-4
27
20
R3
#8
62 in-lbs
#8
62 in-lbs
#4
55 in-lbs
#4
55 in-lbs
#1
35 in-lbs
#1
35 in-lbs
#2
50 in-lbs
# 2
50 in-lbs
ACH580-BxR-034A-4
34
25
R3
#3
55 in-lbs
#3
55 in-lbs
ACH580-BxR-044A-4
44
30
R3
ACH580-BxR-052A-4
52
40
R4
#2
62 in-lbs
#2
62 in-lbs
#2
55 in-lbs
#2
55 in-lbs
#2/0
110 in-lbs
#2/0
110 in-lbs
ACH580-BxR-065A-4
65
50
R4
#1
55 in-lbs
#1
55 in-lbs
ACH580-BxR-077A-4
77
60
R4
#1/0
75 in-lbs
#1/0
75 in-lbs
ACH580-BxR-096A-4
96
75
R5
#1/0
124 in-lbs
Consult
factory
#3/0
275 in-lbs
Consult
factory
#2/0
71 in-lbs
Consult
factory
#1/0
50 in-lbs
Consult
factory
ACH580-BxR-124A-4
124
100
R6
#2/0
124 in-lbs
250 MCM
275 in-lbs
300 MCM
301 in-lbs
ACH580-BxR-156A-4
156
125
R7
#3/0
124 in-lbs
300 MCM
275 in-lbs
500 MCM
372 in-lbs
ACH580-BxR-180A-4
180
150
R7
ACH580-BxR-240A-4
240
200
R8
350
MCM
274 in-lbs
350
MCM
274 in-lbs
2 X 500
MCM
372 in-lbs
1)
“BxR” represents both BCR and BDR.