ACH580 Installation, Operation and Maintenance Manual
77
ACH580-01 Installation
80A0
AI supervision
Programmable fault:
12.03 AI supervision
function
An analog signal is
outside the limits
specified for the analog
input.
Check signal level at the analog input.
Check the auxiliary code.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter group
12 Standard AI
.
0001
AI1LessMIN
0002
AI1GreaterMAX
0003
AI2LessMIN.
0004
AI2GreaterMAX
80B0
Signal supervision 1
(Editable message text)
Programmable fault:
32.06 Supervision 1 action
Fault generated by the
signal supervision
function 1.
Check the source of the fault
(parameter
32.07 Supervision 1
signal
).
80B1
Signal supervision 2
(Editable message text)
Programmable fault:
32.16 Supervision 2 action
Fault generated by the
signal supervision
function 2.
Check the source of the fault
(parameter
32.17 Supervision 2
signal
).
80B2
Signal supervision 3
(Editable message text)
Programmable fault:
32.26 Supervision 3 action
Fault generated by the
signal supervision
function 3.
Check the source of the fault
(parameter
32.27 Supervision 3
signal
).
80B3
Signal supervision 4
(Editable message text)
Programmable fault:
32.36 Supervision 4 action
Fault generated by the
signal supervision
function 4.
Check the source of the fault
(parameter
32.37 Supervision 4
signal
).
80B4
Signal supervision 5
(Editable message text)
Programmable fault:
32.46 Supervision 5 action
Fault generated by the
signal supervision
function 5.
Check the source of the fault
(parameter
32.47 Supervision 5
signal
).
80B5
Signal supervision 6
(Editable message text)
Programmable fault:
32.56 Supervision 6 action
Fault generated by the
signal supervision
function 6.
Check the source of the fault
(parameter
32.57 Supervision 6
signal
).
9081
External fault 1
(Editable message text)
Programmable fault:
31.01
External event 1 source
31.02 External event 1
type
Fault in external device
1.
Check the external device.
Check setting of parameter
31.01
External event 1 source
.
9082
External fault 2
(Editable message text)
Programmable fault:
31.03
External event 2 source
31.04 External event 2
type
Fault in external device
2.
Check the external device.
Check setting of parameter
31.03
External event 2 source
.
Code
(hex)
Fault / Aux. code
Cause
What to do