78
ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
9083
External fault 3
(Editable message text)
Programmable fault:
31.05
External event 3 source
31.06 External event 3
type
Fault in external
device 3.
Check the external device.
Check setting of parameter
31.05
External event 3 source
.
9084
External fault 4
(Editable message text)
Programmable fault:
31.07
External event 4 source
31.08 External event 4
type
Fault in external
device 4.
Check the external device.
Check setting of parameter
31.07
External event 4 source
.
9085
External fault 5
(Editable message text)
Programmable fault:
31.09
External event 5 source
31.10 External event 5
type
Fault in external
device 5.
Check the external device.
Check setting of parameter
31.09
External event 5 source
.
FA81
Safe torque off 1
Safe torque off function
is active, ie. STO circuit
1 is broken.
Check safety circuit connections. For
more information, see chapter
The
Safe torque off function
in the
Hardware manual
of the drive and
parameter
31.22 STO indication run/
stop
.
Check the value of parameter
95.04
Control board supply
.
FA82
Safe torque off 2
Safe torque off function
is active, ie. STO circuit
2 is broken.
FF61
ID run
Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group
99 Motor data
.
Check that no external control system
is connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits prevent
the completion of the ID run. Restore
parameters to default settings and try
again.
Check that the motor shaft is not
locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
0001
Maximum current limit
too low.
Check settings of parameters
99.06
Motor nominal current
and
30.17
Maximum current
. Make sure that
30.17
>
99.06
.
Check that the drive is dimensioned
correctly according to the motor.
Code
(hex)
Fault / Aux. code
Cause
What to do