
7
FIRE, EXPLOSION OR CARBON
MONOXIDE POISONING HAZARD
Failure to replace proper controls
could result in fire, explosion or
carbon monoxide poisoning. Failure
to follow safety warnings exactly
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
and liquids in the vicinity of this
appliance.
WARNING
LIVE ELECTRICAL
During installation, testing, servicing,
and troubleshooting of the equipment
it may be necessary to work with live
electrical
components.
Only
a
qualified
licensed
electrician
or
individual properly trained in handling
live
electrical
components
shall
perform these tasks.
Standard
NFPA-70E,
an
OSHA
regulation requiring an Arc Flash
Boundary to be field established and
marked for identification of where
appropriate
Personal
Protective
Equipment (PPE) be worn, should be
followed.
WARNING
GROUNDING REQUIRED
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
electrical code requirements. Failure
to follow code requirements could
result in serious injury or death.
Provide
proper
unit
ground
in
accordance
with
these
code
requirements.
WARNING
ROTATING COMPONENTS
Unit contains fans with moving parts
that can cause serious injury. Do not
remove grill containing fans until the
power
to
the
unit
has
been
disconnected and fan has stopped
rotating.
WARNING
3-PHASE ROTATION
Rotation must be checked on all
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service
technician.
Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
should
be
checked
for
proper
operation. Alterations should only be
made at the unit power connection
CAUTION
Содержание CB-024
Страница 40: ...40 Refrigerant Piping Diagrams Figure 12 A C only piping AHU above CU ...
Страница 41: ...41 Figure 13 A C only piping AHU below CU ...
Страница 42: ...42 Figure 14 Modulating hot gas reheat piping AHU above CU ...
Страница 43: ...43 Figure 15 Modulating hot gas reheat piping AHU below CU ...
Страница 44: ...44 Figure 16 Hot gas bypass piping AHU above CU ...
Страница 45: ...45 Figure 17 Hot gas bypass piping AHU below CU ...
Страница 46: ...46 Figure 18 Modulating hot gas reheat with hot gas bypass piping AHU above CU ...
Страница 47: ...47 Figure 19 Modulating hot gas reheat with hot gas bypass piping AHU below CU ...
Страница 48: ...48 Figure 20 Heat pump piping AHU above CU ...
Страница 49: ...49 Figure 21 Heat pump piping AHU below CU ...
Страница 50: ...50 Figure 22 Heat pump with modulating hot gas reheat piping AHU above CU ...
Страница 51: ...51 Figure 23 Heat pump with modulating hot gas reheat AHU below CU ...