32
Figure 7 - Variable Capacity Compressor
Controller
Low Voltage Terminals
24COM
Module Common
24VAC
Module Power
C1 & C2
Demand Input
P1
Pressure Common
P2
Pressure Input
P3
Pressure Power 5VDC
P4
Pressure Shield
P5 & P6
Pressure Output
T1 & T2
Discharge Temperature Sensor
High Voltage Terminals
A1 & A2
Alarm Relay Out
M1 & M2
Contactor
L1
Control Voltage N
L2
Control Voltage L
U1 & U2
Digital Unloader Solenoid
V1 & V2
Vapor Injection Solenoid
The compressor controller modulates the
compressor unloader solenoid in an on/off
pattern according the capacity demand
signal of the system. The following table
shows the linear relationship between the
demand signal and compressor capacity
modulation. The compressor controller also
protects the compressor against high
discharge temperature. Refer to Table 7 for
the
relationship
between
thermistor
temperature readings and resistance values.
Table 6 - Demand Signal vs. Compressor Capacity Modulation
Demand
Signal (VDC)
Loaded %
Unloaded %
Time Loaded
Time
Unloaded
% Compressor
Capacity
1.00
Off
Off
Off
Off
0%
1.44
10%
90%
1.5 sec
13.5 sec
10%
3.00
50%
50%
7.5 sec
7.5 sec
50%
4.20
80%
20%
12 sec
3 sec
80%
5.00
100%
0%
15 sec
0 sec
100%
To avoid damaging the compressor
controller, DO NOT connect wires to
terminals C3, C4, T3, T4, T5, or T6.
WARNING
Содержание CB-024
Страница 40: ...40 Refrigerant Piping Diagrams Figure 12 A C only piping AHU above CU ...
Страница 41: ...41 Figure 13 A C only piping AHU below CU ...
Страница 42: ...42 Figure 14 Modulating hot gas reheat piping AHU above CU ...
Страница 43: ...43 Figure 15 Modulating hot gas reheat piping AHU below CU ...
Страница 44: ...44 Figure 16 Hot gas bypass piping AHU above CU ...
Страница 45: ...45 Figure 17 Hot gas bypass piping AHU below CU ...
Страница 46: ...46 Figure 18 Modulating hot gas reheat with hot gas bypass piping AHU above CU ...
Страница 47: ...47 Figure 19 Modulating hot gas reheat with hot gas bypass piping AHU below CU ...
Страница 48: ...48 Figure 20 Heat pump piping AHU above CU ...
Страница 49: ...49 Figure 21 Heat pump piping AHU below CU ...
Страница 50: ...50 Figure 22 Heat pump with modulating hot gas reheat piping AHU above CU ...
Страница 51: ...51 Figure 23 Heat pump with modulating hot gas reheat AHU below CU ...