9
TABLE 2. HEATER PERFORMANCE DATA BTP MODELS
MODELS
STORAGE
CAPACITY
U.S. GALLONS
IMPUT RATING BTU/HR.
RECOVERY RATE
GPH@100°F RISE
RECOVERY RATE
GPH@140°F RISE
MAXIMUM
AMPERES
120V, 60Hz, 10
BTP-139/A
81
140,000
136
97
5
BTP-199/A
81
199,000
193
138
5
BTP-270/A
81
270,000
262
187
5
BTP-370/A
81
370,000
359
256
5
Models with letter
³
A
´
following the model number have the optional ASME tank
F
onstru
F
tion
The BTP-370 is available in natural gas only
TABLE 3. GAS AND ELECTRICAL CHARACTERISTICS
Model
Type of Gas
Gas Supply Pressure
Gas Manifold Pressure
Volts/Hz
Amperes
Minimum
Maximum
All Models
Natural
4
5" W
C
(1
12 kPa)
14" W
C
(3
48 kPa)
3
5" W
C
(0
87 kPa)
120/60
<5
All Models
* Propane
4
5" W
C
(1
12 kPa)
14" W
C
(3
48kPa)
3
5" W
C
(0
87 kPa)
120/60
<5
* Model BTP-370(A) is not available in Propane