Breathing Hazard - Carbon Monoxide Gas
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
Under no circumstances should
the input exceed the rate shown
on the water heater’s rating label.
Overfiring could result in damage to
the water heater and sooting.
Gas and carbon monoxide detectors
are available.
Installations above 2000 feet (610 meters) require
repla
F
ement of burner orifi
F
es in a
FF
ordan
F
e with
F
urrent
edition of the National Fuel Gas Code (ANSI Z223
1)
For
Canadian installations
F
onsult Canadian Installations Code
CAN/CSA B149
1
Failure to repla
F
e orifi
F
es will result in
improper and ineffi
F
ient operation of the water heater resulting
in the produ
F
tion of in
F
reased levels of
F
arbon monoxide gas
in ex
F
ess of safe limits whi
F
h
F
ould result in serious personal
injury or death
You should
F
onta
F
t your gas supplier for any spe
F
ifi
F
F
hanges
whi
F
h may be required in your area
As the elevation above sea level is in
F
reased, there is less
oxygen per
F
ubi
F
foot of air
Therefore, the heater input rate
should be redu
F
ed at high altitudes for satisfa
F
tory operation
with the redu
F
ed oxygen supply
Failure to make this redu
F
tion
would result in an over firing of the heater
F
ausing sooting,
poor
F
ombustion and/or unsatisfa
F
tory heater performan
F
e
Ratings spe
F
i
¿
ed by manufa
F
turers for most applian
F
es apply
for elevations up to 2000 feet (610m)
For elevations above
2000 feet (610), ratings must be redu
F
ed at the rate of 4
for ea
F
h 1000 feet (305m) above sea level
For example, if a
heater is rated at 78,000 Btuh (22
9 Kwh) at sea level, to rate
the heater at 4000 feet (1219m), you subtra
F
t 4 (on
F
e for ea
F
h
thousand feet) x
04 (4
input redu
F
tion) x 78,000 (original
rating) from the original rating
Therefore, to
F
al
F
ulate the input rating at 4,000 feet (1219m)
4 x
04 x 78,000
12,480 Btuh (3
7 Kwh), 78,000 (22
9 Kwh) -
12,480 (3
7 Kwh)
65,520 Btuh (19
2 Kwh)
At 6000 feet (1829m)
the
F
orre
F
t input rating should be 59,280 Btuh (17
4 Kwh)
CIRCULATING PUMP WIRING DIAGRAM
STORAGE TANK OR BUILDING RECIRCULATION
FIELD SUPPLIED TEMPERATURE CONTROL
INSTALLED IN THE STORAGE TANK
OR CIRCULATING LOOP RETURN LINE
CIRC
PUMP
MOTOR
L1 HOT
L2 NEUTRAL
120 VAC
POWER
NOTE:
USE SEPARATE 120 VAC POWER
SUPPLY FOR PUMP CIRCUIT. DO NOT
SHARE POWER WITH WATER HEATER AS THIS
MAY CAUSE ELECTRICAL LINE NOISE AND
LEAD TO ERRATIC CONTROL SYSTEM
OPERATION.
FIGURE 8.
CIRCULATING PUMP WIRING DIAGRAM
DISHWASHER LOOP WITH TOGGLE SWITCH
FIELD SUPPLIED TEMPERATURE
CONTROL INSTALLED IN THE
CIRCULATING LOOP RETURN LINE
DISHWASHER
TOGGLE
SWITCH
CIRC
PUMP
MOTOR
L1 HOT
L2 NEUTRAL
120 VAC
POWER
NOTE:
USE SEPARATE 120 VAC POWER
SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE
POWER WITH WATER HEATER AS THIS MAY
CAUSE ELECTRICAL LINE NOISE AND LEAD
TO ERRATIC CONTROL SYSTEM OPERATION.
FIGURE 9.
HIGH ALTITUDE INSTALLATIONS
Fire and Explosion Hazard
Gas and carbon monoxide detectors are
available.
Overfiring could result in fire or
explosion.
Under no circumstances should the
input exceed the rate shown on the
water heater’s rating label.
Содержание 104 Series
Страница 25: ...25 LIGHTING OPERATION LABEL FIGURE 21 LABEL FOR NATURAL AND LP GAS MODELS...
Страница 53: ...NOTES 53...
Страница 54: ...NOTES 54...