78 / 121
User Manual 3000SP
Rev. 1.1 16/03/2021
Identification: MD-AL-GI-00
Rev. 1.1 of 16/03/2021 - Application: GID
4.
After pulling up the AC switch, the countdown will start according to the country code set (for
CEI021-Internal, it will be 300s) to reconnect to the grid. During this period, check that the
household loads are only powered by the grid and that there are no other power flows from either
the photovoltaic system or the battery.
5.
Once the countdown is over, the batteries will start to deliver power according to the availability
towards the utility, trying to reset the consumption from the grid. During this period, check that the
a.
value of the consumption remains constant
*
as the power supplied by the battery increases
during discharge.
b.
The power taken from the grid should decrease by an amount equal to the power supplied by
the battery.
c.
The photovoltaic value on the display remains zero.
6.
Switch on the photovoltaic inverter.