Identification: MD-AL-GI-00
Rev. 1.1 of 16/03/2021 - Application: GID
4.
Start the 3000 SP storage inverter
Supply DC power to the inverter by correctly switching on the batteries:
In the case of Pylontech batteries, set the POWER switch of the battery, or (in the case of
multiple units) of all the batteries, to I (ON position), then press the red SW button of the master
battery for about one second; at this point the LEDs of all the batteries will light up in sequence,
and after a few seconds will turn off, except for the RUN indicating LED.
Figure 50 – Battery status after setting the POWER switch to ON and pressing the SW button
In the case of WeCo batteries, press the RUN button for about one second; after releasing it, wait
for the sound inside the battery indicating the closure of the relay. Repeat the operation for all
the subsequent batteries in the system.
Figure 51 - View of WeCo battery ON button
c)
Supply AC power through the dedicated protection switch of the storage inverter. If there is
more than one switch protecting the inverter (e.g. a circuit breaker and differential switch), they
must all be set to ON to allow the inverter to be connected to the grid.