165
Switch Settings
sense input. If a sense input is not being used, its jumper should be in the “B” (pull-up)
position.
Table 10: Power Supply Board Jumpers
Switch Settings
There are two switches (SW1 and SW2). Each switch package has 8 individual switches
for a total of 16 switches. See
for details of the individual switch blocks, and
on page
for their locations on the transponder PCB.
The primary function of these switches is to set the address of the Model 620x. Each
Model 620x must have a unique address that is also known by the FSA Server. Each
station must have a primary Model 620x. If a station has another Model 620x, then that
one is considered the secondary Model 620x. Primary Model 620xs have addresses that
are less than 512 and secondary Model 620xs have addresses equal to the primary unit
address plus 512. Ten switches are used to select the Model 620x address in binary. Each
address switch in the “ON” position indicates a binary “1” while the “OFF” position
indicates a binary “0”.
Figure 54: Detail of Switches 1 & 2 on Station Transponder Board
Two of the switches on SW1 are associated with the serial port at connector J1. SW1-8 is
used to select the mode of operation for the port, and SW1-7 selects the Software
Configuration Program baud rate. The usual baud rate is 9600 (SW1-7 ON). See the
following table for the descriptions of SW2 and SW1.
Jumper
Configures
Position A
Position B
JP1
Sense Input 4
Floating
Pulled Up (default)
JP2
Sense Input 3
Floating
Pulled Up (default)
JP3
Sense Input 2
Floating
Pulled Up (default)
JP4
Sense Input 1
Floating
Pulled Up (default)
Note
No jumper is equivalent to position “A” (floating).
1
2
3
4
5
6
7
8
OFF
ON
(2 + 8 + 16 = 26)
OFF = 0
1 2 4 8 16 32 64 128
ON = 1
Summary of Contents for 025-9581M
Page 1: ...Fire Station Alerting System Installation and Maintenance 025 9581M ...
Page 6: ...6 025 9581M ...
Page 40: ...Creating Console Positions 40 025 9581M ...
Page 45: ...45 Installing the VoIP Gateway Server ...
Page 78: ...Configuring Station Transponder Units 78 025 9581M ...
Page 124: ...Installing the Station Transponder Units on Site 124 025 9581M ...
Page 146: ...Using a Model 26 Fire Station Dispatcher for System Backup 146 025 9581M ...
Page 188: ...Appendix C Using a Model 620x in a Model 26 based System 188 025 9581M ...
Page 196: ...Fire Station Alerting System Installation and Maintenance 196 025 9581M ...