Installing the Station Transponder Units on Site
120
Setting Receive Levels at the VoIP Server
♦
To set the VoIP Server sound card levels
1. Set the FSA Station Unit pots
R63
and
R64
at mid range (see
2. Set IP-FSA server’s Windows Control Panel sound mixer’s playback
Wave
and
Master
gains to max.
3. Mute all sources in the sound mixer playback except
Master
and
Wave
.
4. Have someone speak into the FSA Station while measuring the voice output at the
IP-FSA server, after the Audio and Digital Input Interface (P/N 950-0690). Into a
600 ohm load, this level should be 1.1 Vpp (-15 dBu rms). For a 60% deviation
sine wave test tone, this would be a level of 0.28 Vrms (-8.8 dBu rms).
5. Adjust the dispatch console’s input gain to accept the IP-FSA output level
observed using the console’s input audio adjustment procedure. If the console is a
Zetron Series 4000, see the audio level setting procedure for the dual channel card
in the installation manual (P/N 025-9533).
Note
This procedure will be easier to perform if you temporarily connect
an Station Transponder Unit to the network at the VoIP Server
location. If this is not possible, you must arrange for an assistant to
make the required measurements on site and relay them back to
the location of the server.
Note
If the system is going to have radios installed as a permanent
backup to the VoIP intercom cards, check that jumper JP-14 has a
summing jumper in all of the Station Transponder Units (this is
standard). See
Summary of Contents for 025-9581M
Page 1: ...Fire Station Alerting System Installation and Maintenance 025 9581M ...
Page 6: ...6 025 9581M ...
Page 40: ...Creating Console Positions 40 025 9581M ...
Page 45: ...45 Installing the VoIP Gateway Server ...
Page 78: ...Configuring Station Transponder Units 78 025 9581M ...
Page 124: ...Installing the Station Transponder Units on Site 124 025 9581M ...
Page 146: ...Using a Model 26 Fire Station Dispatcher for System Backup 146 025 9581M ...
Page 188: ...Appendix C Using a Model 620x in a Model 26 based System 188 025 9581M ...
Page 196: ...Fire Station Alerting System Installation and Maintenance 196 025 9581M ...