User Manual 3PH HYD5000-HYD20000-ZSS
Rev. 1.1 16/03/2021
Identification: MD-AL-GI-00
Rev. 1. of 16/03/2021 - Application: GID
104/138
ID020
HwADFaultVGrid(
AC)
Grid
voltage
(AC)
measurement error
ID021
GFCIDeviceFault(
DC)
Current (DC) leakage
measurement error
ID022
GFCIDeviceFault(
AC)
Current (AC) leakage
measurement error
ID023
HwADFaultDCV
Measurement error of
the DCI component of
the charge voltage
ID024
HwADFaultIdc
Input
current
measurement error
ID029
ConsistentFault_G
FCI
Leakage current reading
error
ID030
ConsistentFault_V
grid
Grid voltage reading
error
ID033
SpiCommFault
(DC)
SPI
communication
error (DC)
ID034
SpiCommFault
(AC)
SPI
communication
error (AC)
ID035
SChip_Fault
Chip error (DC)
ID036
MChip_Fault
Chip error (AC)
ID037
HwAuxPowerFaul
t
Auxiliary power error
ID041
RelayFail
Relay detection error
ID042
IsoFault
Low
impedance
isolation
Check the isolation resistance
between the photovoltaic panels and
the ground, if there is a short circuit,
the error can be fixed immediately.
ID043
PEConnectFault
Ground fault
Check the Ac-side of the PE output
for grounding.
ID044
PvConfigError
Error in input mode
setting.
Check the mode of the PV input
(parallel/independent); if they are
not correct, change them.
ID045
CTDisconnect
CT error
Check whether the CT connection is
correct.
ID049
TempFault_Bat
Battery
temperature
protection
Make sure that the inverter is
installed in a cool, well-ventilated
place, below the temperature limits
ID050
TempFault_HeatSi
Radiator
temperature