User Manual 3PH HYD5000-HYD20000-ZSS
Rev. 1.1 16/03/2021
Identification: MD-AL-GI-00
Rev. 1. of 16/03/2021 - Application: GID
105/138
nk1
protection 1
and away from direct sunlight. Check
that the inverter has been installed
according to the instructions in the
manual.
ID051
TempFault_HeatSi
nk2
Radiator
temperature
protection 2
ID052
TempFault_HeatSi
n3
Radiator
temperature
protection 3
ID053
TempFault_HeatSi
nk4
Radiator
temperature
protection 4
ID054
TempFault_HeatSi
n5
Radiator
temperature
protection 5
ID055
TempFault_HeatSi
n6
Radiator
temperature
protection 6
ID057
TempFault_Env1
Ambient
temperature
protection 1
ID058
TempFault_Env2
Ambient
temperature
protection 2
ID059
TempFault_Inv1
Module 1 temperature
protection
ID060
TempFault_Inv2
Module 2 temperature
protection
ID061
TempFault_Inv3
Module 3 temperature
protection
ID065
VbusRmsUnbalanc
e
RMS bus voltage is not
balanced
Internal inverter errors. Switch it off,
wait 5 minutes and switch it on
again. If the errors still occur, contact
technical support.
ID066
VbusInstantUnbal
ance
Transient voltage value
of the BUS is not
balanced
ID067
BusUVP
Busbar
undervoltage
during grid connection
ID068
BusZVP
Low BUS voltage
ID069
PVOVP
PV overvoltage
Check whether the voltage of the PV
modules in series (Voc) is higher
than the maximum input voltage. If
so, adjust the number of PV modules
in series to reduce the voltage of the
PV modules in series, adapting them
to the input voltage range of the
inverter. After changing the voltage,
the inverter returns to normal
operation on its own.