User Manual 3PH HYD5000-HYD20000-ZSS
Rev. 1.1 16/03/2021
Identification: MD-AL-GI-00
Rev. 1. of 16/03/2021 - Application: GID
66/138
3.
Enter the number “701”:
a.
From the first screen where the number “600” appears, press the “→” key once to write
the number “601”.
b.
Press “
SET
” twice to move the cursor left, highlighting “601”;
c.
Press the “→” key once more to write the number “701”
Note
: In case of error, press “ESC” and then “SET” again to reset the required code.
4.
Confirm by pressing
SET
and to enter the settings menu.
5.
Enter the following menus and set the parameters indicated:
a.
CT
:
i.
Press
SET
to enter the menu
ii.
Write “40”:
1.
From the first screen where the number “1” appears, press the ”→” key several times
to write the number “10”.
2.
Press “
SET
” once to move the cursor left, highlighting “10”
3.
Press the “→” key several times to write the number “40”
Note
: In case of error, press “SET” until the number relating to thousands is highlighted
and then press “→” until only the number “1” appears;
at this point repeat the above procedure.
iii.
Press “ESC” to confirm and “→” to scroll to the next setting.
b.
ADDRESS
:
i.
Press
SET
to enter the menu:
ii.
Write “02” (pressing “→” once from screen “01”). With address 02, the inverter assigns
the data sent by the meter as production power. A maximum of 3 meters can be set for
the production (Addresses 02 03 04).