User Manual 3PH HYD5000-HYD20000-ZSS
Rev. 1.1 16/03/2021
Identification: MD-AL-GI-00
Rev. 1. of 16/03/2021 - Application: GID
26/138
2.
Insert the exposed core wires into the OT terminal and crimp them using a crimping tool.
Figure 12 - Crimping of the exposed core
3.
Install the crimped OT terminal, insert the M5 screw and tighten the screw at a torque of 3Nm
using the hex key.
NB:
L3 is the length between the insulating layer of the ground cable, the L4 curved part and
the core wires protruding from the secured part.
NB:
The cavity formed on the conductor just below the crimping strip must completely wrap
the core wires, which must be in contact with the terminal.
Figure 13 - Installation of crimped terminal
1)
M5 screw
2)
OT Terminal
3)
Threaded hole