THE
POWER
OF
RELIABILITY
INNOVATIVE CIRCUIT TECHNOLOGY LTD.
855-334-001
ICT
INSTRUCTION MANUAL
DC SITE CONVERTERS
DIMENSIONS IN INCHES
OUTLINE DRAWING
19.00
3.47
12.33
OUTPUT
INPUT
REMOTE / STATUS CONNECTOR
REMOTE / STATUS CONNECTOR
DC CONNECTOR
WIRE SIZES: #2 - #14 CU/ #8 AL
ALTERNATE RACK EAR POSITION
Input
Voltage
Range
Output
Voltage
Output
Current
(Cont.)
Output
Current
(Peak)
Current
Limiting
Line
Regulation
Load
Regulation
Output
Ripple
(Max)
Efficiency
(Typ @ 48V In)
ICT206012-70AI2
ICT206012-100AI2
20-60 VDC
13.8 VDC
+/- 300 mV
64.0 Amps 70.0 Amps
74.0 Amps
+/- 5%
20mV RMS
90%
Input
Current
@ Vin(min)
55 Amps
78 Amps
13.8 VDC
+/- 300 mV
96.0 Amps 105.0 Amps
110.0 Amps
+/- 5%
20mV RMS
90%
20-60 VDC
Model
Number
0.5%
3.0%
0.5%
3.0%
Operating
Temperature
Range
-20°C to +40°C
-20°C to +40°C
SPECIFICATIONS
PIN 1: COMMON
PIN 2: NC
PIN 3: NO
PIN 4: SD +
PIN 5: SD -
1
2
3
4
5
REMOTE STATUS (COMMON, NC, NO)
The Common, NC, and NO contacts of a small Form C relay are
provided for alarm monitoring. A voltage comparator monitors the
output voltage of the system and drives the relay. When the output
voltage is good the NO pin is connected to the COMMON pin. The
relay is rated 1A / 30VDC.
REMOTE SHUTDOWN (SD+, SD-)
When 5-15Vdc is applied between these two pins, the
output of the unit is disabled. Please observe polarity.
Output
Adjust
(Typ)
12.5 -
14.5 VDC
12.5 -
14.5 VDC
Under / Over
Voltage Shutdown
< 20 VDC /
> 60 VDC
< 20 VDC /
> 60 VDC
ICT206024-35AI2
20-60 VDC
27.6 VDC
+/- 300 mV
25.0 -
29.0 VDC
32.0 Amps 35.0 Amps
37.0 Amps
+/- 5%
< 20 VDC /
> 60 VDC
0.5%
3.0%
20mV RMS
90%
55 Amps
-20°C to +40°C
ICT206024-50AI2
20-60 VDC
27.6 VDC
+/- 300 mV
25.0 -
29.0 VDC
< 20 VDC /
> 60 VDC
0.5%
3.0%
20mV RMS
90%
78 Amps
-20°C to +40°C
48.0 Amps 50.0 Amps
52.0 Amps
+/- 5%