YX3000 Senseless Vector Type Inverter Manual
- 66 -
P4.22
DO max pulse
output freq.
0.1K
~
20.0K
(
max 20KHz
)
0.1KH
z
10.0KHz
○
P4.23
Set counts given
F4.20
~
9999
1
0
○
P4.24
Specified
counts
given
0
~
F4.19
1
0
○
P4.25
Overload
pre-alarm
detection level
20
%~
200
%
1
130
%
○
P4.26
Overload pre-alarm
delay time
0.0
~
20.0s
0.1s
5.0s
○
P5 Group: Protection function parameter
Func
Code
Name
Range
Min
Unit
Factory
default
Modify
P5.00
Motor
overload
protection
mode selection
0
:
Stop outputting
1
:
Inaction
1
0
×
P5.01
Motor
overload
protection
coefficient
20
~
120
%
1
100
%
×
P5.02
Overvoltage
stall
Selection
0
:
Prohibited
1
:
Allowed
1
1
×
P5.03
Overvoltage stall point
380V
:
120
~
150
%
220V
:
110
~
130
%
1
%
140
%
120
%
○
P5.04
Auto current limit level
110
%~
200
%
1
%
150
%
×
P5.05
Freq. drop rate during
current limit
0.00
~
99.99Hz/s
0.01H
z/s
10.00Hz/
s
○
P5.06
Auto current limit
mode selection
0
:
Constant speed invalid
1
:
Constant speed valid
Note: Acc/Dec valid
1
1
×
P5.07
Restart setting after
power failure
0
:
Inaction
1
:
Action
1
0
×
P5.08
Restart waiting time
after power failure
0.0
~
10.0s
0.1s
0.5s
×
P5.09
Fault
self-recovery
times
0
~
10
0
:
Self-recovery invalid
Note: Self-recovery invalid
in overload or overheat
1
0
×
P5.10
Self-recovery interval
time
0.5
~
20.0s
0.1s
5.0s
×
P5.11
Output missing phase
protection
0
:
Inaction
1
:
Action
1
0
○