YX3000 Senseless Vector Type Inverter Manual
- 93 -
(2) After JOG running command is canceled, the inverter will decelerate by Dec time.
P3.09
Communication
configuration
Range: 000
~
155
0
User can configure the baud rate, data format and communication mode by setting P3.09
LED unit’s digit (baud rate):
0
:
1200BPS
1
:
2400BPS
2
:
4800BPS
3
:
9600BPS
4
:
19200BPS
5
:
38400BPS
LED ten’s digit (data format):
0
:
1
-
7
-
2 Format, without check
;
1-initial place, 7-data place, 2-stop place, without check.
1
:
1
-
7
-
1 Format, odd parity check
;
1-initial place, 7-data place, 1-stop place, odd parity
check.
2
:
1
-
7
-
1 Format, even parity check
;
1-initial place, 7-data place, 1-stop place, even parity
check
3
:
1
-
8
-
2 Format, without check
;
1-initial place, 8-data place, 2-stop place, without check.
4
:
1
-
8
-
1 Format, odd parity check
;
1-initial place, 8-data place, 1-stop place, odd parity
check
5
:
1
-
8
-
1 Format, even parity check
;
1-initial place, 8-data place, 1-stop place, even parity
check.
6
:
1
-
8
-
1 Format, even parity check
;
1-initial place, 8-data place, 1-stop place, without
check.
LED hundred’s digit ( communication mode):
0: MODBUS
,
ASCII Mode: MODBUS communication protocol, ASCII data transmission
1: MODBUS
,
RTU Mode: MODBUS communication protocol, RTU data transmission