YX3000 Senseless Vector Type Inverter Manual
- 110 -
Fig.6-25 swing freq. upper/lower limit
20
:
Set running time arrival. When inverter total running time (P3.40) reaches set running
time (P3.39), it outputs index signal.
21:
upper pressure alarm signal. On closed-loop control, Inverter output alarm signal when
the pipeline pressure is greater than the upper limit of pressure.
22:
Lower pressure alarm signal. On closed-loop control, Inverter output alarm signal when
the pipeline pressure is lower than the lower limit of pressure.
P4.14
Freq arrival detection
range(FAR)
Range: 0.00
~
50.00Hz
5.00Hz
This function is a complement to function 1 listed in Table 6-6. When inverter output
frequency is in the “+ -” detection range of set frequency, it outputs pulse signal shown as
Fig.6-25.
Upper limit freq
Lower limit freq
Center freq
Swing freq upper/lower limit