YX3000 Senseless Vector Type Inverter Manual
- 149 -
START
Maintaining no input signal for more than
or equal to 10ms
Address
address
:
8-bit Binary address
Function
Function code
:
8-bit Binary address
DATA
(
n - 1
)
Data content
:
N*8-bit data
,
N<=8
,
less than 8 bytes
……………
DATA 0
CRC CHK Low
CRC Check code
CRC CHK High
16-bit CRC check code is combined with 2
8-bit Binary code
END
Maintaining no input signal for more than
or equal to 10ms
Address
:
00H
:
All broadcast from inverters
01H
:
Communication with inverter of 01 address
0FH
:
Communication with inverter of 15 address
10H
:
Communication with inverter of 15 address, and so on, maximum to 254
(
FEH
)
。
Function and DATA code:
03H
:
Read data from a register
06H
:
Write data to the register.
08H
:
Loop detection.
Function code 03H
:
Read data from a register
:
For example
:
read data from the address 2104H of register (Output current)
ASCII mode
:
Asking for information string format
Answering information string format
Header
“
:
”----3AH
Header
“
:
”----3AH