Input voltage abnormal
Check input power supply
Load abnormal
check load
Inverter capacity is too low
Select inverter with proper capacity
E-04
Acc
overvoltage
Input voltage abnormal
Check input power supply
Acc time is too short
Adjust Acc time
Restart the motor in running
Setup start mode as speed tracking
restart
Fault
code
Type of faults
Possible fault reasons
Troubleshooting
E-05
Dec
overvoltage
Dec time is too short
Adjust the Dec time
Potential load or load inertia is too
big
Add suitable braking device
E-06
Overvoltage
at constant
speed running
Input voltage abnormal
Check input power supply
Acc or Dec time is too short
Adjust the Acc or Dec time
Abnormal change of input
voltage
Mount input reactor
Load inertia is too big
Add suitable braking device
E-07 Overvoltage
of control
power supply
Input voltage abnormal
Check input power supply
E-08
Inverter
overheat
Air duct obstruction
Clean air duct
Environment temperature is too
high
Improve the ventilation or decrease
the carrier frequency
Fan damaged
Replace a new fan
Inverter module abnormal
Contact supplier
E-09
Inverter
overload
Acc time is too short
Adjust Acc time
DC braking value is too high
Decrease DC braking current and increase braking
time
V/F curve setup is not suitable Adjust V/F curve