YX3000 Senseless Vector Type Inverter Manual
- 129 -
。
LED hundred’s digit: PLC state parameter save mode selection
0: No save. Inverter don’t save PLC running state after power failure and
restart from the first stage.
1: Save. Inverter saves PLC running state after power failure, including
running frequency and running time of break stage.
LED thousand’s digit: PLC running time unit
0: Second
1: Minute
The unit only run on PLC stage time definition Validly, PLC operation during deceleration time
unit selection is determined by P0.16.
Note:
(1) PLC for a certain period of time setting 0, means the stage is invalid.
(2) Through the terminal, PLC process can be suspended, failure, operation control,
refer to group P4 terminal related functional parameter group.
P8.01
Stage 1 setting
Range
:
000
-
621
000
a1: Acc time of stage 1 a2: Acc time of stage 2 a3:Acc time of stage 3
d2: Dec time of stage 2 F1: freq of stage 1 F2: freq of stage 2 F3: freq of stage 3
Output freq
Hz
Break signal
a
1
F
1
d
2
a
2
F
2
a
3
F
3
Stage
1
Stage
2
Completed running time
Stage
2
Rest time
Time
t
Fig.6-43 PLC restart mode 1