YX3000 Senseless Vector Type Inverter Manual
- 97 -
P3.38
DC brake current at
0 freq
Range: 0.0
%~
15.0
%
0.0
%
DC brake at 0 freq means inverter output DC voltage to brake motor while freq is 0. Users
can adjust P3.38 to get larger braking force, but the current will be larger.
。
P3.39
Set running time
Range: 0
~
65.535Kh
0.000K
P3.40
Total running time
Range
:
0
~
65.535Kh
*
As total running time reaches set running time, the inverter will output index signal (refer to
P4.08~P4.09).
P3.40 function code defines the total running time of inverter from factory delivery to present.
P3.41
Waiting time for
restart
Range: 00.0
~
60.0s
2.0S
P3.41 is used for setting waiting time for restart at 0 freq. when restart failed, adjusting the
parameter to restart.
P3.42
Output current of
restart
Range: 00.0
~
150.0
%
100.0
%
P3.42 Is used to limit the maximum output current of restart for protection.
P3.43
Displayed parameter
selection 3
Range: 00
~
15
00
This function is used for LED displayed parameter when inverter running. 0-15 relate to
monitoring parameter b-01 to b-15. For example, output current will displayed on LED when
setting P3.43=03. Users can monitor other parameters by pressing ►► key.
P3.44
Displayed parameter
selection 4
Range: 00
~
15
00