The carrier freq. mainly affects the noise of motor and heat loss. The relationship between
carrier freq. and motor noise, leakage current, and interference shown as follow.
Carrier Freq.
Decrease
Increase
Noise
↑
↓
Leakage Current
↓
↑
Interference
↓
↑
Note
:
(1) In order to get better control characteristic, the ratio of carrier frequency to inverter
highest running frequency is suggested beyond 36.
(2) Difference may occur in current value display, when carrier freq. is low.
P0.13
Acc/Dec mode
selection
Range
:
0, 1
0
0: Linear Acc/Dec. Output frequency increases or decreases as constant slope shown as
Fig.6-4.
1: S curve Acc/Dec. Output frequency increases or decreases as s curve shown as Fig.6-5.
Fig.6-4 Linear Acc/Dec
Fig.6-5 S curve Acc/Dec
P0.14
Time of s curve start
stage
Range
:
10.0
%~
50.0
%(
Acc/Dec
),
P0.14
+
P0.15<90
%
20.0
%
t
1
t
2
time
Freq.
Upper limit
Upper limit
Freq.
t
1
t
2
③
②
①
①
②
③
time