6-6
IM 77C01H01-10EN
6.4 D Register Map
D-Reg
No.
Ref No.
H No.
Register
Symbol
Register Name
Effective Range
Initial
Value
Back-
up
R/W
D0074
40074
0049
–
Do not use.
–
–
–
–
D0075
40075
004A
FREQ L
Frequency (float, lower 2 bytes)
45.0 to 65.0 [Hz]
0
X
R
D0076
40076
004B
FREQ H
Frequency (float, upper 2 bytes)
R
D0077
40077
004C
Lead Varh L
LEAD reactive energy (uint32, lower 2 bytes)
0 to 9,999,999 [kvarh]
0 to 9,999,999 [varh]
(Note 1) (Note 5)
0
●
R
D0078
40078
004D
Lead Varh H
LEAD reactive energy (uint32, upper 2 bytes)
R
D0079
40079
004E
Lag Varh L
LAG reactive energy (uint32, lower 2 bytes)
0 to 9,999,999 [kvarh]
0 to 9,999,999 [varh]
(Note 1) (Note 5)
0
●
R
D0080
40080
004F
Lag Varh H
LAG reactive energy (uint32, upper 2 bytes)
R
D0081
40081
0050
Var L
Instantaneous reactive power (float32, lower 2 bytes)
0.1 to ±9,999,999.9 [var]
(Note 1)
0
X
R
D0082
40082
0051
Var H
Instantaneous reactive power (float32, upper 2 bytes)
R
D0083
40083
0052
kVAh L
Apparent energy (lower 2 bytes)
0 to 99,999,999 [kVAh]
0 to 99,999,999 [VAh]
(Note 6)
0
●
R
D0084
40084
0053
kVAh H
Apparent energy (upper 2 bytes)
R
D0085
40085
0054
PULSE2
Pulse unit-2 of electric energy (uint16)
1 to 50,000 [x10varh/pls]
(Note 2)
100
○
* R/W
D0086
40086
0055
–
Do not use.
–
–
–
–
D0087
40087
0056
PULSE2
SLCT
LAG/LEAD/regenerative selection for
pulse output of electric energy
0: LAG pulse,
1: LEAD pulse,
2: Regenerative pulse
(Note 2)
0
○
* R/W
D0088
40088
0057
PULSE2
WIDTH
ON pulse width-2 of electric energy (uint8)
1 to 127 [x10ms]
5
○
* R/W
D0089
40089
0058
Lead kVarh
SET L
LEAD reactive energy - setpoint (uint32, lower 2 bytes)
0 to 9,999,999 [kvarh]
0 to 9,999,999 [varh]
(Note 3) (Note 5)
0
X
W
D0090
40090
0059
Lead kVarh
SET H
LEAD reactive energy - setpoint (uint32, upper 2 bytes)
W
D0091
40091
005A
Lag kVarh
SET L
LAG reactive energy - setpoint (uint32, lower 2 bytes)
0 to 9,999,999 [kvarh]
0 to 9,999,999 [varh]
(Note 3) (Note 5)
0
X
W
D0092
40092
005B
Lag kVarh
SET H
LAG reactive energy - setpoint (uint32, upper 2 bytes)
W
D0093
40093
005C
kVarh RST
Reactive energy reset
If other than 1: Invalid
If 1: Reactive energy
(D0077 to D0080) is reset
X
W
D0094
40094
005D
kVarh STS
Reactive energy writing status
If other than 1: Invalid
If 1: The values of D0089
to D0092 are written as the
integrated value
0
X
W
D0095
40095
005E
kVAh SET L
Apparent energy - setpoint (lower 2 bytes)
0 to 99,999,999 [kVAh]
0 to 99,999,999 [VAh]
(Note 6)
0
X
W
D0096
40096
005F
kVAh SET H
Apparent energy - setpoint (upper 2 bytes)
W
D0097
40097
0060
kVAh RST
Apparent energy reset
If other than 1: Invalid
If 1: Apparent energy
(D0083, D0084) is reset
X
W
D0098
40098
0061
kVAh STS
Apparent energy writing status
If other than 1: Invalid
If 1: The values of D0095
and D0096 are written as
the integrated value
0
X
W
D0099
40099
0062
ADERROR
ADC failure
–
–
R
D0100
40100
0063
ERROR
Various types of error information
–
–
R
D0101
40101
0064
USER
User area (Note 4)
0 to 65535
0
X
R/W
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
D0150
40150
0095
USER
User area (Note 4)
0 to 65535
0
X
R/W
Note 1: The UPM100-xxxx2 allows these registers to be read.
Note 2: The UPM100-xx2x2 and UPM100-xx3x2 allow this register to be read and written.
Note 3: The UPM100-xxxx2 allows these registers to be written.
Note 4: Use the user area when using a display unit from Digital Corporation.
Note 5: For the UPM100-xxxx0 to -xxxx3, the unit is [kvarh].
For the UPM100-xxxx4 to -xxxx7, the unit is [varh].
Note 6: For the UPM100-xxxx0 to -xxxx3, the unit is [kVAh].