8-6
IM 77C01H01-10EN
8.3 Function
< Command: Reading out >
Element FLEN P/U R/W X1
X2
(Data No.) SA BCC ETX CR
Data
&H07
P
R
A
0
ETX CR
&H07
P
R
A
1
ETX CR
&H07
P
R
A
2
ETX CR
&H07
P
R
A
3
ETX CR
&H07
P
R
A
4
ETX CR
&H07
P
R
A
5
ETX CR
&H07
P
R
A
6
ETX CR
&H07
P
R
A
7
ETX CR
&H07
P
R
A
8
ETX CR
&H07
P
R
A
9
ETX CR
< Response: Reading out >
Element FLEN P/U R/W X1
S
SA
Data format
BCC ETX CR
Unit
Data
length
Data
&H07
U
R
A
Batch transfer
58
ETX CR
&H07
U
R
A
□□□□□□□□
Wh
8
ETX CR
&H07
U
R
A
± □.□□□□E±□
W
10
ETX CR
&H07
U
R
A
± □.□□□□E±□
V
10
ETX CR
&H07
U
R
A
± □.□□□□E±□
A
10
ETX CR
&H07
U
R
A
± □.□□□□E±□
var
10
ETX CR
&H07
U
R
A
□□□□□□□□□□
%
10
ETX CR
&H07
U
R
A
Batch transfer
20
ETX CR
Example
To use Category A to send a batch transfer command (active energy, instantaneous
power,voltage, current):
Station address: 01
[Command]
07505241303030314142030D
[Response]
41555241103030313030303030303031 2B362E3531303045 2B312B322E333830
30452B312B382E30 303030452D332D30 2E30303030452D30 20202020202020202020
3542030D
Wh
VA
var
Distortion factor
A
W
V
080304E.EPS
• A thin underline “_“ indicates a command. A thick underline “_“ indicates data to be read
out.
• Response data do not actually have spaces in between. Spaces are inserted in the
example above to make numbers easy to read.
• For analysis of response data, refer to Appendix, “ASCII Code Table.”
• The UPM100 does not measure all-harmonic distortion factor. The measurement is
always “20” (ASCII Code 20 means “blank”).