4-22
IM 77C01H01-10EN
4.3 Communication with Higher-level Devices
FA-M3’s UT Link Module Setup Procedure (Example)
This section explains the procedure for setting up the FA-M3’s UT link module when the
“Automatic mode” is used.
1. Setting Up the UT Link Module
Before following the procedure, always make sure that the FA-M3’s UT link module is
turned off. Then, open the inner cover and follow the setup steps described below.
Configure the DIP switch of the UT link module as shown below:
Switch No.
Status
Description
SW1
ON
Data length: 8 bits
SW2, SW3
ON
Parity: none (default: even)
SW4
OFF
Stop bit: one
SW5
OFF
Checksum: none
SW6
ON
Termination character: yes (CR)
SW7
ON
Mode: Automatic mode
SW8
OFF
Not used.
Set the Baud Rate switch to 9600 bps.
Set the Communication Mode switch to 7 (Normal).
2. Setting Up the UPM100
Set the communication conditions of the UPM100 as shown below:
For details on how to set the conditions, see the user’s manual of Model UPM100 Universal
Power Monitor <Initial Setup Operations> or “1.2 Notes on Setting RS-485 Communication
Conditions” in this manual.
Parameter
Description
Communication protocol
PC link communication (without checksum)
Data length
8 bits
Parity
None
Stop bit
One
Baud rate
9600 bps
3. Turn on the FA-M3.