5.2 Message and Response
Function codes are command words used by the higher-level device to obtain the D
registers information of UPM100.
Table
5-3
Function
Codes
Code
Function
Description
03 Reads data from multiple D registers. Capable of reading data from a maximum of 64
successive registers. (D0001 to D0150)
06 Writes data into D register.
Capable of writing data to one register. (D0001 to D0150)
08 Performs loop back test.
Used when checking communication wiring.
16 Writes data into multiple D registers. Capable of writing data into a maximum of 32 successive
registers. (D0001 to D0150)
• The write function codes will not write into read-only or disabled D registers.
• Broadcast addressing is possible with function codes 06 and 16 only. (Also in this case,
read-only or disabled D registers will not be written.)