3-10
IM 77C01H01-10EN
3.3 Executing Reset Operations
3.3.1
Remote Reset
[Procedure]
1. To execute remote reset, write data to the D register or the I relay in the table below.
The data type is integer.
D Register Reference No.
H No.
I relay
Description
Effective Range
D0059
40059
003A
I0010
Remote reset
If other than 1: Invalid
If 1: UPM100 is reset
Note
• By executing remote reset, the maximum, minimum, and instantaneous voltage and current
values are reset. Remote reset stops while the optional electric energy measuring function is in
operation.
• Even if remote reset is executed, data on active energy, reactive energy, and apparent energy
and the values set to their parameters will be saved.
• The D register and the I relay in the table above have the same functions.
[Example]
To execute remote reset:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
[Command]
[STX] 01010WRW01D0059, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
Note
After remote reset is executed, the micro-computer of the UPM100 is reset. Wait for more than 5
seconds before executing another command.