1-1
IM 77C01H01-10EN
Setup
1
1 Setup
This chapter describes the setup procedure required to use the communication functions
and the communication specifications of the UPM100 universal power monitor.
Hereafter, the UPM100 universal power monitor is simply referred to as the UPM100.
1.1 Setup Procedure
Set up the communication functions on the UPM100 as follows:
Set up the communication function parameters of the UPM100.
For the UPM100 with display function, set up the communication conditions using the
front panel keys.
For the UPM100 without display function, set up the communication conditions using
the front DIP switches. (See the user's manual of Model UPM100 Power Monitor
<Initial Setup Operations>.)
Connect a higher-level device and a UPM100.
(See the user's manual of Model UPM100 Power Monitor <Installation>.)
Create communication programs for the higher-level device to perform communication.
(See "4. PC Link Commnication" or "5. MODBUS Communication" for the communication
protocol. See "6. Functions and Usage of D Registers", "7. Functions and Usage of I
Relays" and "8. UPM01 Communication" for the data storing.)
010101E.EPS
To avoid an electric shock, be sure to turn off the power supply source to the
equipment involved before you start wiring.
Note
• In the case of PLC (MELSEC:Mitsubishi Electric Corporation’s sequencer), “B” is for (-), and “A”
is for (+).
• Do not share the grounding wire with another instrument. Doing so may result in a failure of the
instrument. Use crimp terminals at cable ends.
Note Create communication programs referring to the documentation of each higher-level device.
Higher-level devices : PCs, PLCs (sequencers), touch panels, and others.
Chapter 1 Setup