3-15
IM 77C01H01-10EN
Procedures for Setting UPM100/UPM101 Functions
3
3.4 Other Settings
3.4.3
Start/Stop of Integration
[Procedure]
1. To start/stop integration, write data to the D register in the table below. The data type is
integer.
D Register Reference No. H No.
Description
Effective Range
D0053
40053
0034
Active energy (D0001 and D0002)
Apparent energy (D0083 and D0084)
Regenerative energy (D0067 and D0068)
Reactive energy (D0077 to D0080)
0: Integration is started
1: Integration is stopped
[Example]
To start/stop integration:
For station number 01, use PC link communication (without checksum) and the random write
command as shown below:
<Start>
[Command]
[STX] 01010WRW01D0053, 0000 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]
<Stop>
[Command]
[STX] 01010WRW01D0053, 0001 [ETX] [CR]
[Response]
[STX] 0101OK [ETX] [CR]