4-6
IM 77C01H01-10EN
4.2 Command and Response
The following are the lists of commands available in PC link communication. The details of
them are explained in the description of each command.
1. Bit-basis Access Commands Dedicated to I Relays
Command
Description
Number of bits handled
BRD
Bit-basis read
1 to 164 bits
BWR
Bit-basis write
1 to 164 bits
BRR
Bit-basis, random read
1 to 32 bits
BRW
Bit-basis, random write
1 to 32 bits
BRS
Specifies I relays to be monitored on a bit-by-bit basis.
1 to 32 bits
BRM
Bit-basis monitoring
—
2. Word-basis Access Commands
Command
Description
Number of words handled
WRD
Word-basis read
1 to 64 words
WWR
Word-basis write
1 to 64 words
WRR
Word-basis, random read
1 to 32 words
WRW
Word-basis, random write
1 to 32 words
WRS
Specifies internal registers to be monitored on
a word-by-word basis.
1 to 32 words
WRM
Word-basis monitoring
—
3. Information Commands
Command
Description
Number of monitors handled
INF6
Reads model, suffix codes, and version.
1
INF7
Reads the maximum value of CPU.
1