IM 1E10C1-E
11-3
11. PARAMETER LIST
Indicator
Name
R/W
Description
Data Range, Units
BRAIN
Terminal
Decimal
Point
Default
Value
—
B00
SET
R
—
B01
TAG NO
ASC II 16 characters
W
b02
B02
DAMPING
0.5 to 200 sec
1
3.0
W
b03
B03
FLOW SPAN
1 to 3.0000
0 to 4
1.0000
W
b04
B04
FLOW UNIT
(00) km
3
m
(01) m
3
(02) l
(03) cm
3
(04) M gal
(05) k gal
(06) gal
(07) m gal
(08) k bbl
(09) bbl
(10) m bbl
(11)
µ
bbl
(12) m
(13) ft
b05
B05
TIME UNIT
(00) / d
/ s
W
(01) / h
(02) / m
(03) / s
b06
B06
SIZE UNIT
(00) mm
mm
W
(01) inch
b07
B07
NOMINAL SIZE
1 to 3000.0
1
100.0
W
b08
B08
MF
0.2500 to 3.0000
1.000
W
b10
B10
OUTPUT FUNC
(00) PULSE OUT
PULSE
W
(01) ALARM OUT
OUT
(02) BI DIRECTION
(03) AUTO 2 RANGES
(04) LOW ALARM
(05) TOTAL SWITCH
b11
B11
4 - 20 ALM OUT (00) 2.4 mA OR LESS
21.6 mA
W
(01) 4.0 mA
OR
(02) HOLD
MORE
(03) 21.6 mA OR MORE
b12
B12
POWER FREQ
47.00 to 63.00 Hz
2
50.00
W
Major parameter setting.
Sets tag no. up to 16 characters.
Sets damping time constant of output.
Sets flow span in selected unit.
Selects volume unit of flow span.
Selects time unit of flow span.
Selects flow tube nominal size unit.
Sets flow tube nominal size in selected unit.
Sets meter factor.
Selects status output functions.
Selects current output during alarm
occurrence.
Sets AC power frequency for DC power
(10
-2
X
m)
3
(liter)
(10
3
X
m
3
)