IM 1E10C1-E
6-11
6. OPERATION VIA BRAIN TERMINAL
Display
Description
Press ENTER key twice at an interval of a few seconds.
The display as shown on the left appears.
If the data is correct, press F4 key [OK].
The parameter panel is displayed again.
The setting is completed.
PARAM
B06: SIZE UNIT
inch
B07: NOMINAL SIZE
2.00 inch
B08: MF
1.1200
DATA
DIAG
ESC
SET
B08: MF
1.0000
1.1200
ESC
SET
B08: MF
1.1200
ENTER
×
2
NO
OK
F4
DEL
CLR
6.5.4
Power Frequency (For DC version only)
In case of DC power supply version, setting power frequency is required.
Display
Description
Set the value in areas where the frequency differs in “B12:POWER
FREQ”.
Default: 50.00Hz
PARAM
B10: OUTPUT FUNC
PULSE OUT
B11: 4-20 ALM OUT
21.6mA OR MORE
B12: POWER FREQ
50.00Hz
DATA
DIAG
ESC
6.6 Other Functions
Please set other needed parameters. For detail on the functions, see Chapter 5, “Func-
tions and Settings” except “User-Defined Units” function. For “User-Defined Units”
function, see 6.6.1 below.
6.6.1
User-Defined Units
This function displays the instantaneous flow rate indicated in “A20 FLOW RATE” in
user-defined units.
(1) User-Defined Unit for Instantaneous Flow Rate
Example 1: Displaying the flow rate of a fluid (its specific gravity is 2) in weight (kg)
in a flow rate span of 10 m
3
/h. When the flow rate is 100%, 20,000 kg/h is
displayed.
IMPORTANT