7. OPERATION VIA HART COMMUNICATOR
(7) Burst Mode
The ADMAG SE continuously sends the data stored in it when the burst mode is set
“On”. Either one of instantaneous flow rate, output in %, totalization values and current
output can be selected and sent. The data is sent intermittently as a digital signal when
the ADMAG SE is set in the burst mode.
Setting of Burst Mode
1. Device setup
4. Detailed setup
4. Outputs
3. HART output
4. Burst option
ADMAG SE :
Burst option
********
PV
% range/current
Process vars/crnt
HELP
DEL
ESC
ENTER
Set the data to be sent.
• Instantaneous flow rate (PV)
• Output in % and current output (% range/current)
• Instantaneous flow rate, totalization value* and current
output (Process vars/crnt)
* “Totl”, “Reverse total” or “Diff. total”
Call up “Burst option” display.
3. HART output
3. Burst mode
ADMAG SE :
Burst mode
Off
Off
On
DEL
DEL
ESC
ENTER
1
F4
2
Set “ON” and press ENTER (F4).
Press SEND (F2).
(ENTER)
F2
(SEND)
Call up “Burst mode” display.
ADMAG SE :
HART output
1 Poll addr 0
2 Num req preams 5
3 Burst mode On
4 Burst option PV
HELP
SEND
HOME
ENTER
F4
(ENTER)
F2
(SEND)
Releasing from Burst Mode
Call up “Burst mode” display, and set “Off”.